Specifications
Model:SAO-R2N
Operating current: 100% of the current SV
Operating time characteristics: Inverse type
Operating time: For a 600% overcurrent:
Time scale x 1: 1 to 10 s
Time scale x 4: 4 to 40 s
For a 200% overcurrent:
2.8 x t ±30%, where t is
the operating time at
600% overcurrent.(time SV at max.)
Reset value: More than 95% of the operating current
Operating current accuracy: ±10% of the current SV
Operating time accuracy:
+10/–5% of maximum time SV (at a time SV: 1)
±10% of maximum time SV (at a time SV: 2 to 10)
Influence of temperature on operating current: ±5% for 0 to 40°C; ±10% for –10 to 50°C
Influence of temperature on operating time:±10% for 0 to 40°C; ±20% for –10 to 50°C
(start-up mode)
Influence of frequency on operating time:±5% for a frequency fluctuation of ±5%
(start-up mode)
OMRON Current Sensor As Below:
SAO-R2N
SAO-R5N
SAO-S1N
SAO-S2N
SAO-SS2N
SAO-SU1N
SAO-SU2N
SAO-SU5N